Voltage Drop Calculator

Check how much voltage is lost along a cable run before it reaches the load, in volts and as a percentage.

Not sure? Send us your equipment list.

Tell us what you need to power and we will confirm the exact model, voltage and configuration — usually within 24 hours.

What voltage drop is

Every conductor has resistance, so the voltage at the far end of a cable is always lower than at the source. Current, cable length and conductor size all increase the loss. Above roughly 5% the consequences stop being theoretical: motors run hot and lose torque, contactors chatter, and electronic controls reset themselves.

The formula

Single-phase: Vd = 2 × L × I × ρ ÷ A. Three-phase: Vd = √3 × L × I × ρ ÷ A.

  • L — one-way cable length in metres (the factor 2 in single-phase accounts for the return path).
  • I — current in amps.
  • A — conductor cross-sectional area in mm².
  • ρ — resistivity: 0.0175 Ω·mm²/m for copper, 0.0282 for aluminium, both at 20 °C.

Common questions

What is an acceptable voltage drop?

Most wiring regulations set 3% as a design target for final circuits and 5% as a maximum from the origin of the installation to the furthest point. Beyond 5% motors and electronics start to misbehave.

Why does my result exceed 5% even though the cable is rated for the current?

Because ampacity and voltage drop are two separate checks. A cable can be thermally safe and still lose too much voltage over a long run. Always verify both.

Does this replace a qualified electrician?

No. It is a design aid that uses the standard resistive formula. Final cable selection must also account for installation method, ambient temperature, grouping and local regulations.